We strongly recommend that you check for the following
before connecting the alarm:
• check for Live and Neutral using a two probe tester.
• check for Live using a neon tester.
• check that the Interconnect wire is NOT connected to
Live, Neutral or Earth. Do not use an Earth wire for
the Interconnect line.
N.B. The alarm does not need to be earthed. However the
terminal marked is provided for the convenience of the
installer so that any copper Earth wire or cable coloured
green & yellow, can be safely terminated.
To interconnect the Alarms connect all the IC terminals
together as shown in Figure 4 (see “Interconnecting
Alarms” section on page 14).
4. If the mains wires are recessed, bring the wires
through the rear hole in the mounting plate as shown
in Figure 4.
If the mains wires are being brought along the surface:
(a) position the mounting plate so the cable trunking is
as shown in Figure 4.
(b) the mounting plate has a removable section, take
it out to interface directly with 25mm conduit as shown
in Figure 5. If interfacing to 16mm conduit carefully cut
around the marked section, leaving the top intact and
replace the section. (If you are not using surface wiring,
the removable section must be left in place for electrical
safety reasons).
There are two other positions which are also suitable for
the surface wiring to enter (and exit) the alarm, one next
to the removable section and another directly opposite.
5. Carefully align the mounting plate and screw into
place. Connect the wires to the terminal block. With
recessed wiring, ensure the rear gasket seals around
the edge of the hole in the ceiling or wall. This is to
13
REMOVEABLE
TRUNKING DOOR FOR
Figure 4
Figure 5